Standard Accessories | ||
Power Cord Power Adapter |
1pcs | |
Voltage Test Leads | (2m) * 5 pcs | |
Alligator Clip | 5pcs | |
Soft Carry Bag | 1pcs | |
Sticker of input port | 1pcs | |
CD(Software+User's Guide) | 1 |
Selection Table | |
Model | SA2200 |
Standard compliance | IEC61000-4-30 Class A |
Voltage/Current | ● |
Frequency | ●50Hz, 60Hz, 400Hz |
Dips/swell | ● |
Harmonics | ● 1-100th(50/60Hz) |
Power and energy | ● |
Unbalance | ● |
Monitor | ● |
Inrush | ● |
Flicker | ● |
Transients | ●163.84kS/s |
Logger | ● |
Wave Recording | ● |
Input Characteristics | |
Channel(Voltage/Current) | 4 /4 |
Voltage Range | 1-1000Vrms, 6000V transient voltage |
Current Range | depends on supplied current clamp |
PC Software Analysis | ● |
Micro SD card(bulid-in) | 32GB |
Battery | Lithium ion, 5200mAh/>8h |
Time Synchronization | GPS/Beidou(option) |
Communication | |
interface | USB Host, LAN, WIFI |
WIFI App | ●(option) |
General Characteristic | |
Screen | 5.6' TFT LCD with resolution640*480(SA2200) |
Dimension/Weight | 270*190*66mm/2.0kg |
Wire Combinations | 1Ø+NEUTRAL,1Ø SPLIT PHASE,1Ø IT NO NEUTRAL,3Ø WYE, 3Ø DELTA, 3Ø IT, 3Ø HIGH LEG, 3Ø OPEN LEG, 2-ELEMENT, 2 1/2-ELEMENT |
Electrical Safety | IEC61010-1 ,Safety Degree: 600V CAT IV 1000V CAT III |
Measurement | |||
Measurement Range | Resolution | Accuracy | |
Voltage/Current/Frequency | |||
Vrms(AC+DC) | 1 ~ 120Vrms | 0.001Vrms | ±0.1% of nominal voltage |
120Vrms~400Vrms | 0.01Vrms | ||
400Vrms~1000Vrms | 0.1Vrms | ||
Vpk | 1 ~ 1400Vpk | 0.01Vpk | ±0.5% of nominal voltage |
V(Crest Factor) | 1.0 ~ >2.8 | 0.01 | ±5% |
Arms(AC) 10mV/A 1mV/A | |||
0~150A | 0.01A | ±0.1%±0.1A | |
1~2000A | 0.01A | ±0.1%±0.1A | |
10~6000A | 0.01A | ±0.1%±0.2A | |
A(Crest Factor) | 1 ~ 10 | 0.01 | ±5% |
Frequency | 42.5~57.5(50Hz nominal) | 0.01Hz | ±0.01Hz |
51~69(60Hz nominal) | 0.01Hz | ±0.01Hz | |
320~480(400Hz nominal) | 0.01Hz | ±0.01Hz | |
Dips & Swells | |||
Vrms1/2 | 0 ~ 200% of nominal voltage | 0.01Vrms | ±0.2% |
Arms1/2 | depends on current clamps | 0.01A | ±1% |
Harmonic (IEC61000-4-7) | |||
Harmonic Number | 1 ~ 100(50/60Hz) (IEC61000-4-7) 1~12(400Hz) | ||
Harmonic Voltage %f | 0.0 ~ 100.0% | 0.01% | ±0.1% ± nx0.1% |
Harmonic Current %f | 0.0 ~ 100.0% | 0.01% | ±0.1% ± nx0.1% |
THD | 0.0 ~ 100.0% | 0.01% | ±2.5% |
Phase | -180° ~180° | 0.1° | ± nx0.1° |
Power and Energy | |||
P, S, Q1 | Max. 6000MW | 0.1kW | ±1%±10 digits |
PF & cosФ | 0 ~ 1 | 0.01 | ±0.01 |
kWh, kVAh, kvarh | depends on nominal voltage and current clamps | ±1%±10 digits | |
Flicker (IEC61000-4-15) | |||
Pst(10min)/Plt (2 hrs) | 0.00 ~ 20.00 | 0.01 | ±5% |
Unbalance | |||
Voltage | 0.0 ~ 20.0% | 0.1% | ±0.1% |
Current | 0.0 ~ 20.0% | 0.1% | ±1% |
Voltage Phase | -360° ~ 0° | 0.1° | ±0.1° |
Current Phase | -360° ~ 0° | 0.1° | ±0.5° |
Voltage Transient | |||
Vpk | ±6000Vpk | 0.01V | ±15% |
Vrms | 10 ~ 1000Vrms | 0.01V | ±2.5% |
Min. Test Time | 6.5us | ||
Inrush Current | |||
Arms | depends on current clamps | 0.01 | ±1% ± 5digits |
Inrush Duration | 1 ~ 32min selectable | 10ms | ±20ms |
Logger | |||
Recording | user-defined parameters for 4 phases at the same time | ||
Memory | Data stored in Micro SD card, 32GB | ||
Duration Time | 2 hrs to 1 year, depends on the recording items and time interval | ||
Interval | 1s to 60 minutes | ||
Monitor | |||
Support EN50160 in default or user-defined standard |